Protect-Air
AirCom -
Service
Order Hotline
+49 2102 7339021Payment methods
PQ4
1
Description:
Closed loop electronic pressure regulator consisting of two
solenoid valves, an internal pressure transducer, and an
electronic control circuit mounted to an integral volume
booster. The pressure is controlled by activating the
solenoid valves, which apply pressure to the pilot side of
the volume booster.
Single loop:
Pressure is controlled by two solenoid valves. One valve
functions as inlet control, the other as exhaust. The pressure
outlet is measured by an internal pressure transducer which
provides a feedback signal to the electronic controls.
This feedback signal is compared with the command input signal.
Any difference between the two signals causes one of the two
solenoid valves to open, allowing flow into or out of the system.
Accurate pressure is maintained by these two valves.
Media: dry, unlubricated and 5 μm filtered compressed air or non-corrosive gases
Pressure range: 0 ... 35 bar
Accuracy: +/- 0.4%
Input signal: 0-10 V; 4-20 mA as an option
Mounting position: any
Protection class: IP65
Adjustment: zero point, span, hysteresis
Response time: 15 ... 20 ms
Air consumption: without constant bleed
Power consumption: 6 W
Temperature range: 0 °C to 70 °C / 32 °F to 158 °F
Booster body: nickel-plated aluminium
Elastomer: FKM, NBR/Buna-N
Transducer: aluminium and silicon
Valves: nickel-plated brass
Closed loop electronic pressure regulator consisting of two
solenoid valves, an internal pressure transducer, and an
electronic control circuit mounted to an integral volume
booster. The pressure is controlled by activating the
solenoid valves, which apply pressure to the pilot side of
the volume booster.
Single loop:
Pressure is controlled by two solenoid valves. One valve
functions as inlet control, the other as exhaust. The pressure
outlet is measured by an internal pressure transducer which
provides a feedback signal to the electronic controls.
This feedback signal is compared with the command input signal.
Any difference between the two signals causes one of the two
solenoid valves to open, allowing flow into or out of the system.
Accurate pressure is maintained by these two valves.
Media: dry, unlubricated and 5 μm filtered compressed air or non-corrosive gases
Pressure range: 0 ... 35 bar
Accuracy: +/- 0.4%
Input signal: 0-10 V; 4-20 mA as an option
Mounting position: any
Protection class: IP65
Adjustment: zero point, span, hysteresis
Response time: 15 ... 20 ms
Air consumption: without constant bleed
Power consumption: 6 W
Temperature range: 0 °C to 70 °C / 32 °F to 158 °F
Booster body: nickel-plated aluminium
Elastomer: FKM, NBR/Buna-N
Transducer: aluminium and silicon
Valves: nickel-plated brass
Your are now in the overview of an article: PQ4
Choose a version from the table underneath, please.
part number | connection thread | connection | supply pressure max. [bar] | pressure range [bar] | flow rate air [Nl/min] | accuracy in percent [%] | output signal [V] | Price |
---|---|---|---|---|---|---|---|---|
PQ4EE-C1 | 1/2"NPT | 1/2"NPT | 1,0 | 0...0,1 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-C5 | 1/2"NPT | 1/2"NPT | 1,0 | 0...0,5 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-01 | 1/2"NPT | 1/2"NPT | 2,0 | 0...1,0 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-02 | 1/2"NPT | 1/2"NPT | 3,0 | 0...2,0 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-04 | 1/2"NPT | 1/2"NPT | 7,0 | 0...4,0 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-06 | 1/2"NPT | 1/2"NPT | 7,0 | 0...6,0 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-08 | 1/2"NPT | 1/2"NPT | 9,0 | 0...8,0 | 2000 | 0,4 | 0-10 | 1484,74 € |
PQ4EE-10 | 1/2"NPT | 1/2"NPT | 15 | 0...10 | 2000 | 0,4 | 0-10 | 1484,74 € |