Protect-Air
AirCom -
Service
Order Hotline
+49 2102 7339021Payment methods
PCEX
12
Piezo-operated proportional pressure regulator with closed loop in a
two-wire system. Outlet pressure is proportional to an electrical
input signal. The valve can be mounted in any position and is
immune to shock or vibration. It is pilot-controlled to reach a
higher flow rate.
Media: lubricated or unlubricated and 50 μm filtered compressed air
or non-corrosive gases
Supply voltage:
not necessary due to two-wire system
(supply through 4...20 mA command signal)
Electrical connector: coupling socket, 4-pin according to DIN 43651,
size 15 x 15 mm connector turnable in 90° steps
ATEX classification: Compliance with directive 2014/34/EU for use in
potentially explosive atmosphere of group IIC,
temperature classification T4.
Ignition protection type: II1G Ex ia IIC T4; II1D Ex D20 T135°C
Power consumption: < 200 mW
Failsafe feature exhaust at power breakdown
Linearity/Hysteresis: < 1% FS Repeatability < 0.5% FS
Mounting position: any
Protection class: IP 65
Air consumption: The pilot valve has an air consumption of 1.6 l/min
Temperature range:
Media = 0 °C to 60 °C / 32 °F to 140 °F
Ambient = 0 °C to 60 °C / 32 °F to 140 °F
Body: aluminium and plastic
Elastomer: NBR/Buna-N and FKM
Inner valve: stainless steel and plastic
two-wire system. Outlet pressure is proportional to an electrical
input signal. The valve can be mounted in any position and is
immune to shock or vibration. It is pilot-controlled to reach a
higher flow rate.
Media: lubricated or unlubricated and 50 μm filtered compressed air
or non-corrosive gases
Supply voltage:
not necessary due to two-wire system
(supply through 4...20 mA command signal)
Electrical connector: coupling socket, 4-pin according to DIN 43651,
size 15 x 15 mm connector turnable in 90° steps
ATEX classification: Compliance with directive 2014/34/EU for use in
potentially explosive atmosphere of group IIC,
temperature classification T4.
Ignition protection type: II1G Ex ia IIC T4; II1D Ex D20 T135°C
Power consumption: < 200 mW
Failsafe feature exhaust at power breakdown
Linearity/Hysteresis: < 1% FS Repeatability < 0.5% FS
Mounting position: any
Protection class: IP 65
Air consumption: The pilot valve has an air consumption of 1.6 l/min
Temperature range:
Media = 0 °C to 60 °C / 32 °F to 140 °F
Ambient = 0 °C to 60 °C / 32 °F to 140 °F
Body: aluminium and plastic
Elastomer: NBR/Buna-N and FKM
Inner valve: stainless steel and plastic
Your are now in the overview of an article: PCEX
Choose a version from the table underneath, please.
part number | connection thread | connection | supply pressure max. [bar] | pressure range [bar] | flow rate air [Nl/min] | Kv [m³/h] | Price |
---|---|---|---|---|---|---|---|
PCEX-02 | G1/8 | G1/8 | 3 | 0...2,0 | 550 | 0,5 | 1381,33 € |
PCEX-03 | G1/8 | G1/8 | 5 | 0...3,0 | 550 | 0,5 | 1381,33 € |
PCEX-04 | G1/8 | G1/8 | 6 | 0...4,0 | 550 | 0,5 | 1381,33 € |
PCEX-05 | G1/8 | G1/8 | 8 | 0...5,0 | 550 | 0,5 | 1381,33 € |
PCEX-06 | G1/8 | G1/8 | 8 | 0...6,0 | 550 | 0,5 | 1381,33 € |
Cart
Products:
0 Pieces
Total:
0,00 €
Leaflet
Products:
0 Pieces
Total:
0,00 €